VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-24
04 - 08
Digital Input Terminal Response Time
Factory Setting: 01
Settings 01~20
This parameter selects the response time of digital input terminals MI1 to MI8, EF, REV and FWD.
AC drive will scan the digital input terminals once every 2msec. During each scan the drive will
check the status of each terminal (open or closed).
In noisy environments, it would be advantageous to verify the terminal status several times before
executing a new command, nearly eliminating false signals.
Example: If Pr.04-08 is set to 4, the AC drive will confirm the terminal status (4+1 = 5) 5 times
before a change is made. This correlates to an 8~10msec time response from input command to
execution.
It is not recommended to set this parameter to 00, since interference may cause improper operation
of the AC drive.
04 - 09
AVI Minimum Voltage
Factory Setting: 0.0
04 - 10
AVI Maximum Voltage
Factory Setting: 10.0
Settings 0.0 ~ 10.0V Unit: 0.1
04 - 11
AVI Minimum Frequency (percentage of Pr.1-00)
Factory Setting: 0.00
04 - 12
AVI Maximum Frequency (percentage of Pr.1-00)
Factory Setting: 100.00
Settings 0.00~100.00% Unit: 0.01
04 - 13
ACI1 Minimum Current
Factory Setting: 4.0
04 - 14
ACI1 Maximum Current
Factory Setting: 20.0
Settings 0.0 ~ 20.0mA Unit: 0.1
04 - 15
ACI1 Minimum Frequency (percentage of Pr.1-00)
Factory Setting: 0.00
04 - 16
ACI1 Maximum Frequency (percentage of Pr.1-00)
Factory Setting: 100.00
Settings 0.0~100.0% Unit: 0.01
04 - 17
ACI2 Minimum Current
Factory Setting: 4.0
04 - 18
ACI2 Maximum Current
Factory Setting: 20.0
Settings 0.0 ~ 20.0mA Unit: 0.1