VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-6
Parameters Functions Settings
Factory
Setting
Customer
02-13 Master Frequency Memory
Setting
00: Do not remember the last
known frequency
01: Remember the last known
frequency
01
02-14 Source of Second Frequency
Command
00: Master Frequency Setting is
controlled by PID controller.
01: Master frequency is controlled
by an external terminal via
analog input AVI: DC
0~+10V.
02: Master frequency is controlled
by an external terminal via
analog input ACI1: DC 4~
20mA.
03: Master frequency is controlled
by an external terminal via
analog input ACI2: DC 4~
20mA
04: Master frequency is handled
via RS485 serial
communication (RJ-11).
05: External Reference Master
frequency via External
Reference.
00
02-15 Source of Second Operation
Command
00: Controlled by the digital
keypad
01: Controlled by the external
terminals, keypad STOP
enabled.
02: Controlled by the external
terminals, keypad STOP
disabled
03: Controlled by the RS-485
communication interface
keypad STOP enabled.
04: Controlled by the RS-485
communication interface
keypad STOP disabled.
00
02-16 Loss of ACI Signal 00-Highest operational frequency 00