VFD-F Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-12
02 - 06
Line Start Lockout
Factory Setting: 01
Settings 00: Enabled
01: Disabled
02: If the command to run still remains after
resetting, the inverter will continue to run.
When enabled, the AC drive will not start when powered up with a run command applied. The AC
drive must see the run command transition from stop to run after power up. When Line Start
Lockout is disabled (also known as Auto-Start), the AC drive will start when powered-up with run
commands applied.
Pr02-06=2
This determines the following matter. The VFD (Variable-Frequency Drive) detects an error message and
eliminates the error. If the command terminal remains running in the external function terminals, you can
simply press the RESET button to make the VFD running again.
02 - 07
ACI4~20mALoss of ACI Signal
Factory Setting: 01
Settings 00: Decelerate to 0Hz
01: E.F.
02: Continue operation by the last frequency command
03: Use loss of ACI Signal Frequency of Pr02-16
This parameter determines the AC drives response to a loss of the ACI input.
02 - 08
Start-up Display Selection
Factory Setting: 00
Settings Bit0~1: 00 = F LED
01 = H LED
10 = U LED (special display)
11 = Fwd / Rev
Bit2: 0 = Fwd LED / 1 = Rev LED
Bit3~5: 000 = 1st 7-step
001 = 2nd 7-step
010 = 3rd 7-step
011 = 4th 7-step
100 = 5th 7-step
Bit6~7: Reserved
This parameter determines the display on keypad after each power up.