Setting Functions Descriptions
21 Low voltage detection The corresponding output will be closed when the
DC Bus voltage drops below our threshold. The
keypad will display “Lu”.
22 Operation Mode indication The corresponding output will be closed when the
AC drives “Operation Command” is controlled by
the external terminals.
23 Fault Indication The corresponding output will be closed when AC
drive has experienced a fault.
24 Master Frequency Attained 1 The corresponding output will be closed when the
AC drives output frequency exceeds (Pr.03-08)
Master Frequency Attained 1.
25 Master Frequency Attained 2 The corresponding output will be closed when the
AC drives output frequency exceeds (Pr.03-09)
Master Frequency Attained 2.
26 Over Temperature indication The corresponding output will be closed when the
AC drive temperature exceeds its rating.
27 Drive Ready The corresponding output will be closed the when
the AC drive is ready and has no faults.
28 External Emergency Stop (EF1) The corresponding output will be closed when
multi-function input terminals (Pr.04-00 to 04-07)
are set to emergency stop and then activated.
29 Software brake output The corresponding output will be closed when the
AC drives DC bus voltage exceeds (Pr.08-19) the
brake level.
30 OL or OL1 overload warning The corresponding output will be closed upon an
overload (OL or OL1) fault.
31 Dwell indication (sleep) The corresponding output will be closed when the
AC drive is in a Dwell status (Pr.11-07).
32 Low current indication The corresponding output will be closed when the
AC drives output current is lower than the Low
Current setting (Pr.06-08).
33 PID feedback error indication The corresponding output will be closed when the
PID feedback signal has an error.
34 PLC Program Running
The Output will be activated when PLC Program is
running.
35 PLC Program Step Completed
The Output will be activated for 0.5 sec when each
multi-step speed is attained.
36 PLC Program Completed
The output will be activated for 0.5 sec when the
PLC program cycle has completed
37 PLC Operation Paused
The output will be activated when PLC operation is
paused.
38
Loss of an ACI signal Indication
When there is a loss of an ACI signal indication, the
corresponding relay output will be closed.
39
HOA-Hand mode indication
Under the Hand mode indication of HOA mode, the
corresponding relay output will be closed.