5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-9
1 - 13 Jog Acceleration/Deceleration Time Factory Setting: d 10.0
Settings d 0.1 to d 600Sec Unit: 0.1Sec
This parameter can be set during operation.
1 - 14 Jog Frekvencia Factory Setting: d 6.0
Settings d 1.0 to d 400Hz Unit: 0.1Hz
This parameter can be set during operation.
! The JOG function can be selected using Multi-function Input terminals (Pr.4-04 to
Pr.4-08) if programmed for Jog (d10). When the Jog terminal is “closed”, the AC drive
will accelerate from Minimum Output Frequency (Pr.1-05) to Jog Frequency (Pr.1-14).
When the Jog terminal “open”, the AC drive will decelerate from Jog Frequency to zero.
The acceleration/deceleration time is decided by the Jog acceleration/deceleration time
(Pr.1-13). During operation, the AC drive cannot perform Jog command. And during Jog
operation, other operation commands cannot be accepted, except command of
FORWARD, REVERSE and STOP keys on the digital keypad.
Frequency
Max.
Output
freq.
Pr.1-00
Jog
Freq.
Pr.1-14
Acceleration Time
Deceleration Time
Time
Jog operation
command
ON
OFF
Pr. 1-13
Pr. 1-13