5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-57
Tartalom
Tár cím
Funkciók
Status monitor
Read only
2100H 21: Reserved
22: CPU failure (cF3.1)
23: CPU failure (cF3.2)
24: CPU failure (cF3.3)
25: CPU failure (cF3.4)
26: CPU failure (cF3.5)
27: CPU failure (cF3.6)
28: CPU failure (cF3.7)
29: Hardware protection failure (HPF.1)
30: Hardware protection failure (HPF.2)
31: Hardware protection failure (HPF.3)
32: CE 10
33: doG
34: SErr
35: ErEd
36: PID error
Status of AC Drive
00: RUN LED light off, STOP LED light up
01: RUN LED blink, STOP LED light up
10: RUN LED light up, STOP LED blink
Bit 0-1
11: RUN LED light up, STOP LED light off
Bit 2 01: Jog active
00: REV LED light off, FWD LED light up
01: REV LED blink, FWD LED light up
10: REV LED light up, FWD LED blink
Bit 3-4
11: REV LED light up, FRD LED light off
Bit 5-7 Not used
2101H
Bit 8 1: Main freq. Controlled by communication
Bit 9 1: Main freq. Controlled by external terminal
Bit 10
1: Operation command controlled by communication
Bit 11 1: Parameters have been locked
Bit 12-15 Not Used
2102H Frequency command F (XXX.XX)
2103H Output Frequency H (XXX.XX)
2104H Output Current A (XXX.XX)
2105H DC-BUS Voltage U (XXX.XX)
2106H Output Voltage E (XXX.XX)
2107H Step number of Multi-Step Speed Operation
2108H Step number of PLC operation
2109H Time of PLC Operation
210AH Counter Value