VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-50
3.2 ADR (Communication Address)
Valid communication addresses are in the range of 0 to 254. Communication address
equals to 0 means broadcast to all AC drives (AMD), in this case, the AMD will not reply
any message to the master device.
For example, communication to AMD with address 16 decimal:
ASCII mode: (ADR 1, ADR 0) =’1’,’0’ ‘1’=31H, ‘0’=30H
RTU mode: (ADR) = 10H
3.3 CMD (Command code) and DATA (data characters)
The format of data characters depends on the command code. The available
command codes are described as followed: Command code: 03H, read N words. The
maximum value of N is 12. For example, reading continuous 2 words from starting
address 2102H of AMD with address 01H.
ASCII mód:
Command message: Response message:
STX ‘:’ STX ‘:’
‘0’ ‘0’ ADR 1
ADR 0
‘1’
ADR 1
ADR 0
‘1’
‘0’ ‘0’ CMD 1
CMD 0
‘3’
CMD 1
CMD 0
‘3’
‘2’ ‘0’
‘1’
Number of data
(count by byte)
‘4’
‘0’ ‘1’
Starting data
address
‘2’ ‘7’
‘0’ ‘7’
‘0’
Content of starting data
address 2102H
‘0’
‘0’ ‘0’
Number of data
(count by word)
‘2’ ‘0’
‘D’ ‘0’ LRC CHK 1
LRC CHK 0
‘7’
Content of data address
2103H
‘0’
CR ‘7’ END 1
END 0
LF
LRC CHK 1
LRC CHK 0
‘1’
CR
END 1
END 0
LF
RTU mód:
Command message: Response message:
ADR 01H ADR 01H
CMD 03H CMD 03H
21H Starting data address
02H
Number of data (count by byte) 04H
00H 17H Number of data
(count by word)
02H
Content of data address 2102H
70H
CRC CHK Low 6FH 00H
CRC CHK High F7H
Content of data address 2103H
00H
CRC CHK Low FEH
CRC CHK High 5CH