3 - 02 Desired Frequency Attained Factory Setting: d 1.0
Settings d 1.0 to d 400 Hz Unit: 0.1Hz
! If a Multi-function output terminal is set to function as Desired Frequency Attained
(Pr.3-05 or 3-06=d9), then the output will be activated when the programmed frequency
is attained.
Desired Freq.
Detection
range
-2Hz
Detection range
+
-
4Hz
Detection range
+
-
2Hz
Time
Freq.
Max. Output
Freq.
Pr.3-02
ON
ON
OFF
OFF
OFF
OFF
Preset Freq.
Attained
indication
Pr.3-05 to 3-06
Desired Freq.
Attained
Indication
Pr.3-05 to 3-06
Desired Freq. Attained & Preset Freq. Attained
3 - 03 Terminal Count Value Factory Setting: d 0
Settings d 0 to d 999
! The parameter determines the value of the internal counter. The internal counter can be
triggered by the external terminal (Pr.4-4 to Pr.4-8, d19). Upon completion of counting, the
specified output terminal will be activated. (Pr.3-05, Pr.3-06, d14).
3 - 04 Preliminary Count Value Factory Setting: d 0
Settings d 0 to d 999
! When the counter value is counted up from “1” to the setting value of this parameter, the
corresponding multi-function output terminal will be closed, when sets d15 as desired
value attained setting. The application can be that closing the multi-function output
terminal makes the AC drive operates at low speed until stop before the counting value is
going to be attained.