d13, d14 External Base Block:
Parameter values d13, d14 program Multi-Function Input Terminals: M1 (Pr.4-04), M2
(Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) for external Base Block control. Value
d13 is for normally open (N.O.) input, and value d14 is for a normally closed (N.C.) input.
GND
B.B.(N.O.)
setting by d13
B.B.(N.C.)
setting by d14
Mx "Close": Operation available.
Mx "Open":Operation available.
Note: When a Base-Block signal is received, the AC drive will stop all output and the motor
will free run. When base block control is deactivated, the AC drive will start its speed
search function and synchronize with the motor speed, and then accelerate to Master
Frequency.
External
base-block
signal
Output
frequency
Output
voltage
Speed search starts with the
reference value
Pr.8-06
Min. base-block time
Speed search operation
Pr.8-04=d1
Speed synchronization
detection
d15, d16 Increase/Decrease Master Frequency:
Parameter values d15, d16 program the Multi-Function Input Terminals: M1 (Pr.4-04), M2
(Pr.4-05), M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to incrementally increase/ decrease
the Master Frequency each time an input is received.
GND
setting by d15
setting by d16
Mx "Close": Freq. will increase
by one unit.
Mx "Close":Freq. will decrease
by one unit.