d20 Counter Reset:
Parameter value d20 programs Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr. 4-05),
M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08) to reset the counter.
GND
d20 reset the counter
value.
Mx "close": reset counter.
Reset counter
d21 Select ACI / Deselect AVI:
Parameter value d21 allows the user to select the input type ACI or AVI via an external
switch. AVI is selected when the contact is open and ACI is selected when the contact is
closed. Please note: the use of this feature will override Pr.2-00 programming and the
jumper of the front of the drive must be moved to the correct location either across the AVI
or ACI pin head.
4- 09 Line Start Lockout Factory Setting: d 0
Settings: d0 Disable
d1 Enable
! When enabled, the AC drive will not start when powered up with run commands applied.
To start in Line Start Lockout mode, the AC drive must see the run command go from
stop to run after power up. When Line Start Lockout is disable (also known as
Auto-Start), the drive will start when powered-up with run commands applied.
4- 10 Up/down frequency command mode Factory Setting: d 3
Settings: d0 up/down frequency by acceleration/deceleration time
d1 up frequency according to constant speed, down frequency
according to deceleration time
d2 up frequency according to acceleration time, down frequency
according to constant speed
d3 up/down frequency by constant speed
4- 11 Acceleration/Deceleration speed of constant up/down
frequency
Factory Setting: d 1
Settings: d0 to d1000 Hz/sec Unit: 5 Hz/sec
! This parameter is used to set the acceleration/deceleration speed mode when
multi-function terminal is set to up/down frequency. (Pr. 4-04 ~ Pr.4-08, function d15,