VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-22
Example 5:
In this example a 1 volt negative bias is used. In a noise environment, it is advantageous to
use negative bias to provide a noise margin (1V in this example).
Example 6:
In this example, a negative bias is used to provide a noise margin. Also a potentiometer
frequency gain is used to allow the Maximum Output Frequency to be reached.
Example 7:
In this example, the potentiometer is programmed to run a motor is both forward and reverse
direction. A motor will be idle when the potentiometer position is at mid-point of its scale.
Using Pr.4-03 will disable the external FWD and REV controls.
Hz
0V
10V
0
60
Potentiometer Scale
Max.
Output
Freq.
Pr.1-00
Factory Settings
Pr.1-00=60Hz--Max. output Freq.
Pr.4-00=30Hz--Potentiometer bias freq.
Pr.4-01=1 -- bias polarity
Pr.4-02=200% -- pot. freq. gain
Pr.4-03=1 -- pot. REV motion enable
60Hz
30Hz
0Hz
0V
5V
10V
30Hz
60Hz
REV
FWD
REV.
FWD.
60