Túlnyomaték felismerési szintje
Factory Setting: d 150
Settings d 30 to d 200% Unit: 1%
! A setting of proportional to the Rated Output Current of the drive.
6 - 05 Time setting for Over-torque Detection Factory Setting: d 0.1
Settings d 0.1 to d 10.0 sec Unit: 0.1sec
! If a Multi-Function Output Terminal is set as Over-Torque Detection Indication and the
output current exceeds the Over-Torque Detection Level (Pr.6-04, Factory Setting:
150%), the Over-Torque Detection Time (Pr.6-05, Factory setting: 0.1) and the setting of
multi-function terminal is Over-Torque Detection Indication, the contact will be “close”.
6 - 06 Electronic Thermal Overload Relay Selection Factory Setting: d 2
Settings d 0 Reduce Torque Motor
d 1 Constant Torque Motor
d 2 Inactive
! This function is used to limit the output power of the AC drive when powering a
“self-cooled motor” at low speed.
6 - 07 Electronic Thermal Characteristic Factory Setting: d 60
Settings d 30 to d 600Sec Unit: 1 Sec
This parameter can be set during operation.
! The parameter determines the time required activating the I
2
t electronic thermal
protection function. The graph below shows I
2
t curves for 150% output power for 1
minute.
1
2
3
4
5
60Hz or more
50Hz
10Hz
5Hz
0
20
40
60
80
100
120
140
160
180 200
Operation
time(min)
Load
factor
(%)