VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-38
6-02 Over-Current Stall Prevention Level Factory Setting: d130
Settings d20 to d150%
Unit: 1%
! A setting of 100% is equal to the Rated Output Current of the drive.
! During acceleration and steady-state operation, the AC drive output current may increase
abruptly to exceed the value specified by Pr.6-02 due to rapid acceleration or excessive
load on the motor. When this function is enabled, the AC drive will decrease. The AC drive
will only resume acceleration when the current drops below the level specified by Pr. 6-02.
Output current
Over-current
detection
level
Pr.6-02
time
Output
frequency
time
Over-current Stall Prevention Level
ON
OFF
Band=5%
6 - 03 Túlnyomaték felismerési módja (OL2) Factory Setting: d 0
Settings d 0 Over-Torque detection disabled.
d 1 Over-Torque detection enabled during constant speed
operation, and continue to run till OL1 or OL.
d 2 Over-Torque detection enabled during constant speed
operation, and operation halted after over-torque
detection.
d 3 Over-Torque detection enabled during running, and
continues to run till OL1 or OL.
d 4 Over-Torque detection enabled during running, and
operation halted after over-torque detection
Vista de pagina 54