5
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-53
RTU mód:
Command message: Response message:
ADR 01H ADR 01H
CMD 10H CMD 10H
05H 05H Starting Data
address
00H
Starting Data
address
00H
00H 00H Number of data
(count by word)
02H
Number of data
(count by word)
02H
CRC CHK Low 41H Number of data
(count by Byte)
04H
CRC CHK High 04H
17H Data content of
address 0500H
70H
03H Data content of
address 0501H
E8H
CRC CHK Low C8H
CRC CHK High 2EH
3.4 CHK (check sum)
ASCII mód:
LRC (Longitudinal Redundancy Check) is calculated by summing up, module 256, the
values of the bytes from ADR1 to last data character then calculating the hexadecimal
representation of the 2’s-complement negation of the sum.
For example, reading 1 word from address 0401H of the AC drive with address 01H
STX ‘:’
‘0’ ADR 1
ADR 0
‘1’
‘0’ CMD 1
CMD 0
‘3’
‘0’
‘4’
‘0’
Starting data
address
‘1’
‘0’
‘0’
‘0’
Number of data
‘1’
‘F’ LRC CHK 1
LRC CHK 0
‘6’
CR END 1
END 0
LF
01H+03H+04H+01H+00H+01H=0AH, the
2’s-complement negation of 0AH is F6H.