
VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-40
6 - 08 Present Fault Record Factory Setting: d 0
6 - 09 Second Most Recent Fault Record Factory Setting: d 0
6 - 10 Third Most Recent Fault Record Factory Setting: d 0
Settings d 0 No fault occurred
d 1 Over-current (oc)
d 2 Over-voltage (ov)
d 3 Overheat (oH)
d 4 Overload (oL)
d 5 Overload1 (oL1)
d 6 External fault (EF)
d 7 Not used
d 8 Not used
d 9 Current exceeds 2 times rated current during acce. (ocA)
d 10 Current exceeds 2 times rated current during dece. (ocd)
d 11 Current exceeds 2 times rated current during steady state
operation (ocn)
d 12 Ground fault (GF)
! Pr.6-08 to 6-10 store records of the three most recent faults that had occurred. Use the
reset key to reset the drive when the fault no longer exits.
Comentarios a estos manuales