VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-24
Explanations:
d0 Parameter Disable:
Enter value (d0) to disable any Multi-Function Input Terminal: M1 (Pr.4-04), M2 (Pr.4-05),
M3 (Pr.4-06), M4 (Pr.4-07) or M5 (Pr.4-08).
Note: The purpose of this function is to provide isolation for unused Multi-Function Input
Terminals. Any unused terminals should be programmed to d0 to insure they have no
effect on drive operation.
d1 Two wire operation: Restricted to Pr.4-04 and external terminals M0, M1.
FWD/STOP
REV/STOP
M0 "Open": Stop, "Close": FWD Run
M1 "Open": Stop, "Close":REV Run
GND
d2 Two wire operation: Restrict to Pr. 4-04 and external terminals M0, M1.
RUN/STOP
REV/FWD
M0 "Open": Stop, "Close": Run
M1 "Open": FWD, "Close":REV
GND
Note: Multi-function Input Terminal M0 does not have its own parameter designation. M0
must be used in conjunction with M1 to operate two and three wire control.
d3 Three Wire Control: Restricted to Pr.4-04 control terminals M0, M1, M2.
STOP RUN
RUN/FWD
M0 Run command, Runs when "close"
M2 Stop command, stops when "Open"
M1 REV/FWD Run selection
"Open": FWD Run
"Close": REV Run
GND
Note: When value d3 is selected for Pr. 4-04, this will over ride any value entered in
Pr.4-05, since Pr.4-05 must be used for three wire control as shown above.