5.8 Group 7: Motor Paraméterek
7 - 00 Motor néveleges áramfelvétele Factory Setting: d 85
Settings d 30 to d 120% Unit: 1%
This parameter can be set during operation.
! This parameter will limit the AC drive output current in order to prevent the motor from
overheating.
7 - 01 Motor terhelés nélküli áramfelvétele Factory Setting: d 50
Settings d 0 to d 90% Unit: 1%
This parameter can be set during operation.
! The rated current of the AC drive is regarded as 100%. Motor setting of no-load current
will effect the slip compensation. The setting value must be less than motor rated
current setting Pr.7-00
7 - 02 Nyomaték kompenzáció Factory Setting: d 1
Settings d 0 to d 10 Unit: 1
This parameter can be set during operation.
! This parameter may be set so that the AC drive will increase its voltage output during
start-up to obtain a higher initial starting torque.
7 - 03 Slip Kompenzásció Factory Setting: d 0.0
Settings d 0.0 to d 10.0 Unit: 0.1
This parameter can be set during operation.
! While driving an asynchronous motor, load on the AC drive will increase, causing an
increase in slip. This parameter may be used to compensate the nominal slip within a
range of 0 to 10. When the output current of the AC drive is greater than the motor
no-load current (Pr.7-01), the AC drive will adjust its output frequency according to this
parameter.