5-62
A - 05 Integration’s Upper Bound Frequency Factory Setting: d100
Settings d0 to d100%
! This parameter determines the integration’s upper frequency limit while operating in the
PID feedback loop. (Limit = 1-00×A-05 %). During a fast Integration response, it is
possible for the frequency to spike beyond a reasonable point. This parameter will limit
this frequency spike.
A - 06 Egyszeri várakozás Factory Setting: d0
Settings d0 to d999 Unit: 2 msec
! One-time delay of PID will slow down oscillation of the system.
! A setting of d0 disables this function.
A - 07 PID Frekvencia kimeneti korlátozása Factory Setting: d100
Settings d0 to d110%
! This parameter determines the limit of the PID Command frequency. If this parameter is
set to 110%, then the maximum output frequency while in the PID operation will be (110%
x Pr.01-00) 66Hz.
A - 08 Detection Time of the Feedback Error Factory Setting: d0.0
Settings d0.0 to d650 seconds
! This parameter defines the detection time for the loss of a feedback analog signal. The
drive will follow the operating procedure programmed in Pr.A-09 if the feedback signal is
lost for more than the time set in Pr. A-08.
! A setting of 0.0 disables this function.
A - 09 Feedback Signal Fault Treatment Factory Setting: d0
Settings d 0 warn and RAMP to stop
d 1 warn and COAST to stop
! This parameter selects the operation of the drive upon a loss of PID feedback signal.
A - 10 Dwell (sleep) Frequency Factory Setting: d0.0
Settings d0.0 to d400Hz