VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
5-32
Example 1 (Pr.5-07 = d1): Execute one cycle of the PLC program. Its relative parameter
settings are:
1. Pr.5-00 to 5-06: 1
st
to 7
th
step speed (sets the frequency of each step speed).
2. Pr.4-04 to 4-08: Multi-Function Input Terminals (set one multi-function terminal as d17-
PLC auto-operation).
3. Pr.3-05 to 3-06: Multi-Function Output Terminals (set a Multi-Function Terminal as
d10-PLC operation indication, d11-one cycle in PLC auto mode or d12-PLC operation
fulfillment attainment).
4. Pr.5-07: PLC mode.
5. Pr.5-08: Direction of operation for Master Frequency and 1
st
to 7
th
step speed.
6. Pr.5-09 to 5-16: operation time setting of Master Frequency and 1
st
to 7
th
step speed.
Frequency
60Hz
50Hz
40Hz
30Hz
20Hz
15Hz
10Hz
0Hz
5-09
5-10
5-11
5-12
5-13
5-14
5-15
Pr.5-00
Pr.5-01
Pr.5-02
Pr.5-03
Pr.5-04
Pr.5-05
Pr.5-06
Master
Freq.
Program operation
command
Program operation
output indication
Program step
complete
Program operation
completed
Master freq.=5Hz
5-00=10 Hz
5-01=20 Hz
5-02=40 Hz
5-03=60 Hz
5-04=50 Hz
5-05=30 Hz
5-06=15 Hz
4-07=d17
3-05=d10
3-06=d11
5-07=d1
5-08=d0
5-09=10 Sec
5-10=10 Sec
5-11=12 Sec
5-12=15 Sec
5-13=15 Sec
5-14=8 Sec
5-15=17 Sec
5-16=17 Sec
5Hz
5-16
Time
(Sec)
Note: The above diagram shows one complete PLC cycle. To restart the cycle, turn the PLC
program off and then back on.