VFD-S Series
DELTA ELECTRONICS, INC. ALL RIGHTS RESERVED
8-6
4 Csoport – BEMENETI FUNKCIÓK PARAMÉTEREZÉS
Parameters Explanation Settings
Factory
Setting
4-00
Potentiometer Bias
Frequency !
d 0.0 - d 100.0% d0.0
4-01
Potentiometer Bias
Polarity !
d0: Positive Bias
d1: Negative Bias
d0
4-02
Potentiometer
Frequency Gain
!
d1 - d200 % d100
4-03
Potenciométeres hátra
forgás negedélyezve
d0: Csak az előreforgás engedélyezve
d1: Reverse Motion enabled
d0
4-04
Multi-Funkciós
bemeneti Terminál 1
(M0, M1)
d0: Paraméter tiktása
d1: FWD/STOP, REV/STOP
d2: FWD/REV, RUN/STOP
d3: 3-wire Operation Control Mode
d4: E.F. External Fault Input (N.O.)
d1
4-05
Multi-Funkciós
bemeneti Terminál 2
(M2)
d5: E.F. External Fault Input (N.C.)
d6: Reset
d7: Multi-Step Speed Command 1
d8: Multi-Step Speed Command 2
d6
4-06
Multi-Funkciós
bemeneti Terminal 3
(M3)
d9: Multi-Step Speed Command 3
d10: Jog Operation
d11: Acceleration/deceleration Speed Inhibit
d12: First or Second Acceleration/deceleration
Time Selection
d7
4-07
Multi-Funkciós
bemeneti Terminál 4
(M4)
d13: Base-Block (B.B.) (N.O.)
d14: Base-Block (B.B.) (N.C.)
d15: Increase Master Frequency
d16: Decrease Master Frequency
d17: Run PLC Program
d8
4-08
Multi-Funkciós
bemeneti Terminál
5(M5)
d18: Pause PLC
d19: Counter Trigger Signal
d20: Counter Reset
d21: Select ACI / Deselect AVI
d22: Disable PID function
d23: JOG FWD
d24: JOG REV
d25: The source of master frequency is AVI.
d26: The source of master frequency is ACI.
d9